Phân loại: ĐIỀU HÒA TỦ ĐIỆN
Mã hàng: ENC-GR1000EX
index
(50/60Hz)
Mounting type | Top-mounting |
---|---|
Cooling capacity(W) | 960 |
Setting Temperature Range(℃) | 25~45 |
Use Area Temperature(℃) | 20~55 |
Use Area Humidity(%RH) | 10~85 (No condensation) |
External dimensions(mm) | H348×W600×D353 |
Weight(kg) | 32 |
Coating Color | Munsell 5Y 7/1 Equivalent color of light beige |
Rated Voltage(V) | Single-phase AC200~240 |
Consumption Current: Rated(A) | 2.9/2.8 |
Consumption Current: MAX(A) | 4.1/4.0 |
Consumption wattage: Rated(W) | 455 |
Consumption wattage: MAX(W) | 659 |
Recommended breaker capacity (A) | 10 |
Vibration Resistance | Equivalent to JIS Z 0200 Level1 |
Dust prevention / dust proof protection class | Equivalent to IP54 (internal circulation route) |
Refrigerant / Fill ration(g) | R1234yf 250g |
Noise (dB (A)) | Approx. 70 |
External Output | Alarm output (No-voltage/normal open: resistive load 250V 2A), Can be switched to no-voltage/normal close by setting |
Display | Internal temperature/Error/RUN |
*Cooling Capacity : Rated capacity value when ambient temperat ure is 35°C and ambient humidity is 40%RH , power source & voltage : 200V. (Measuring specification :JIS B 8615-1 the inside of a air enthalpy test method)
*Use area temperature / humidity : Use area temperature / humi dity is not meant to satisfy all conditions in temperature and humidity.
*Rating Value : 35°C ambient temperature, ambient humidity RH 40%, power source & voltage : 200V.
*Maximum Value : The ambient temperature at MAX value has spec ification separately.
*Use the product keeping the use power supply and voltage; wit hin ±10% of rated power supply and rated voltage.
*Consumption current and wattage are values during cooling ope ration.
*Dust prevention / dust proof protection class : Excluding dra in pipe section
*Reading an instruction manual well certainly before use and p lease use it right.
[Caution]
To ensure proper operation of this equipment, read the operation manual before use.
Depending on model and quantity, separate charter delivery may be arranged (additional costs apply).
Overseas at the time of delivery, we recommend packing for overseas separately.
Please check through the cooler between the FA and the power (circuit breakers) to the appropriate specification of the FA breaker cooler.
Cause of failure and be used at the rated power supply out of range.
Please use the service and maintenance on a regular basis.
Failure to maintain regular maintenance, you may be a factor in product performance degradation trouble.
When the outside temperature is low in winter, please do not let the FA cooler continuous operation.
When disposing of this product, you should comply with various laws and regulations, please go to the appropriate.
APISTE offer various kind of Apiste air conditioner for Control box, Apiste Control panel, Server rack, Heat exchanger and Precision air conditioning system with a wide range of type such as Apiste Inner Lateral-Mount Type. New product from Apiste is Thermography(Thermal Viewer), Apiste FSV 700
Apiste aim to improve reliability for panel cooler.
Apiste are a panel cooler manufacture which provides heat prevention unit.– http://maylanhcongnghiep.net/
Apiste original panel cooler was come up with accumulation of our own know-how and cooling technique.
Apiste is the best company which currently has the achievement in FA cooler market in Japan.
|
|
|